Furnace Selection and Extended Plenum Duct Sizing
The size of the extended plenum (use standard duct)is as shown when the furnace is located:
|
Heat |
Located |
Building
Divided |
Furnace |
|
0-56,000 |
14 x 8 |
10 x 8 & 10 x 8 |
(2) 10 x 8 |
|
57-80,000 |
16 x 8 |
10 x 8 & 12 x 8 |
(2) 10 x 8 |
|
81-108,000 |
22 x 8 |
10 x 8 & 14 x 8 |
(2) 12 x 8 |
|
109-132,000 |
26 x 8 |
10 x 8 & 16 x 8 |
(2) 16 x 8 |
|
133-160,000 |
30 x 8 |
12 x 8 & 22 x 8 |
(2) 16 x 8 |
|
NOTE: If air conditioning is to be used at the present or in the future, the cooling load must be computed and duct size selected on the basis of the larger size indicated, shown below. |
|||
Maximum Applicable Cooling Unit
The size of the extended plenum in inches is as shown when the cooling unit is located:
|
Cooling |
Blower |
Located |
Building
Divided |
Located |
|
0 - 24,000 |
2 Ton (720) |
16 x 8 |
10
x
8
& |
(2) 10 x 8 |
|
25-36,000 |
3 Ton (1080) |
22 x 8 |
10
x
8
& |
(2) 12 x 8 |
|
37-60,000 |
5 Ton (1800) |
30 x 8 |
12
x
8
& |
(2) 16 x 8 |
Return Grille and Return Duct Sizing
Single return. Use one of size shown.
|
Furnace |
Grill
Size |
Duct |
|
to 56,000 |
216 sq. in. |
16" x 8" or 1 joist space |
|
to 80,000 |
270 sq. in. |
16" x 8" or 2 joist spaces |
|
to 108,000 |
405 sq. in. |
26" x 8" & 10" x 8" or 2 joist spaces |
|
to 132,000 |
450 sq. in. |
30" x 8" or 2 joist spaces |
|
to 160,000 |
540 sq. in. |
(2) 20" x 8" or 3 joist spaces |
Two returns. Use two of size shown.
|
Furnace |
Grill
Size |
Duct |
|
to 56,000 |
108 sq. in. |
16" x 8" or 1 joist space |
|
to 80,000 |
162 sq. in. |
16" x 8" or 2 joist spaces |
|
to 108,000 |
216 sq. in. |
26" x 8" or 2 joist spaces |
|
to 132,000 |
244 sq. in. |
30" x 8" or 2 joist spaces |
|
to 160,000 |
285 sq. in. |
(2) 20" x 8" or 3 joist spaces |
|
NOTE:
When
multiple
returns
are
used,
a
preferred
return
system
provides
for
a
return
from
each
room
(except
that
air
usually
is
not
returned
from
the
kitchen
or
bathrooms). |
||
An orifice chart can only be a guide because of varying temperatures and barometric pressures from day to day in various localities. From the below drill sizes, it may be necessary to make adjustments for the most satisfactory operating conditions. Rates based on 2500 BTU/ft.3, manifold pressure 10.5" water column.
High Altitude Corrections
The specifications shown on this chart for orifice sizes are pressures from sea level to approximately 3500 ft. above sea level. For altitudes from 3500 ft. to 5000 ft., use one drill # larger, From 5000 ft. to 6500 ft., use two drill #'s larger. Above 6500 ft., use two or three drill sizes larger.
Refer to NFPA 54 for a comprehensive chart.
|
Wire
Gauge |