Home | Online Ordering | Products | Engineering & Construction | LPG Trucks & Fabrication | TEECO Topics | Contact TEECO | About TEECO |
Products>>Section A- RegO / ECII>>LPG Cylinder and Service Valves>>Page A-12
|
|
|
Tamper Resistant Cylinder Valve with Outlet Check for Vapor Withdrawal
This valve is designed for vapor withdrawal from and protection of DOT cylinders up to 100 lbs. propane capacity. Ideal for cylinders used in the field by construction crews, utility repair men and plumbers.
|
Part Number |
Container Connection |
Service Connection |
Fixed Liquid Level Vent Valve Style |
Pressure relief Valve Setting |
For use in Cylinders with Propane Capacity up to: | Approximate Filling Rate Liquid Flow, GPM | Order | |||
| Pressure Drop Across Valves | ||||||||||
| 10 PSIG | 25 PSIG | 50 PSIG | 100 PSIG | |||||||
| 9103T9F | 3/4 M. NGT | F. POL (CGA 510) | None | 375 PSIG | 100 lbs. | 5.0 | 7.6 | 10.7 | 14.9 | |
Cylinder Valve for RV and Small ASME System Vapor Withdrawal
Designed especially for vapor withdrawal service in small ASME containers with surface area up to 23.8 square feet. UL flow capacity is 645 CFM/air, per NFPA 58.
|
Part Number |
Container Connection |
Service Connection |
Fixed Liquid Level Vent Valve Style |
Pressure relief Valve Setting |
For use in Cylinders w/ Propane Capacity up to: | Flow Capacity SCFM/Air | Order |
| 9106CO | 3/4 M. NGT | F. POL (CGA 510) | None | 312 PSIG | ASME Tanks* | 645 |
* Surface area up to 23.8 square feet.
Cylinder Valve for Liquid Withdrawal
Equipped with excess flow valves and liquid withdrawal tubes, they are designed for liquid withdrawal of DOT cylinders up to 100 lbs. propane capacity. They are most often used with heavy BTU loads found in industrial uses.
|
Part Number |
Container Connection |
Service Connection |
Fixed Liquid Level Vent Valve Style |
Dip Tube Length With Deflector |
Liquid Withdrawal Tube Length | Order |
| 9107K8A | 3/4 M. NGT | CGA 555 | Knurled | 11.6" | 44" |
|
Pressure relief Valve Setting |
For use in Cylinders with Propane Capacity up to: | Approximate Filling Rate Liquid Flow, GPM | Closing Flow (LP Gas)* | |||||
| Vapor | Liquid | |||||||
| Pressure Drop Across Valves | 25 PSIG Inlet | 100 PSIG Inlet | ||||||
| 10 PSIG | 25 PSIG | 50 PSIG | 100 PSIG | |||||
| 375 PSIG | 100 lbs. | 3.3 | 5.4 | 7.7 | 11.1 | 525 SCFH | 1,000 SCFH | 1.7 GPM |
*Closing flows based on 3/8" O.D. withdrawal tube 44" long or less attached. IMPORTANT: 1/4" O.D. pigtails or POL connections for 1/4" O.D. pigtails should not be used with these valves. NOTES: To ensure proper functioning and maximum protection from excess flow valves, the cylinder valve should be fully opened and backseated when in use. These valves incorporate an excess flow valve. Refer to L-500 / Section F, for complete information regarding selection, operation and testing of excess flow valves.
Products>>Section A- RegO / ECII>>LPG Cylinder and Service Valves>>Page A-12